UIS Command Component Parameters
The following tables list and describe the parameters specific to the UIS command component types for this remote device:
For more general information about UIS command component parameters, see UIS Command Components. The DG_F_DEV (Get data group from device) and DG_T_DEV (Send data group to device) command component types are configured in the template file. The other command component types are considered special and are defined in the EIE editor code. See Special UIS Command Component Types for more information.
CLRHSTXA
Clear All History Tx Info clears all historical data group caches. CLRHSTXA has no command parameters.
Note: If you clear all caches using a UIS command, the cache values in each transaction of historical data groups are not reset; past transactions continue to display actual values. This is done for performance reasons so that each DDS transaction does not have to be updated. The driver ignores these cached values after the command has been issued.
CONFIG
Get RTU Configuration retrieves configuration information from the field device. CONFIG has no parameters.
CYUPDTPT
Update CygNet Point updates the record for a CygNet point. CYUPDTPT has the following command parameters:
| Parameter | Required | Description |
|---|---|---|
|
FOnErr |
No |
Fail cmd on update error indicates to abort the UIS command if any update errors are encountered. The errors that might come up include: if the point specified in the Fac, Serv, Site, or UDC parameters does not exist, or if the point exists in a different UIS and any messaging errors or communication failure to that service comes up. |
|
Fac |
Yes |
Facility for pt identifies the facility of the point to update. |
|
Serv |
No |
Service for pt identifies the SERVICE of the point to update. |
|
Site |
No |
Site for pt identifies the SITE of the point to update. |
|
UDC |
Yes |
UDC for pt identifies the UDC of the point to update. |
|
UType |
No |
Update type indicates the type of update. Value options are 0 - 3, where 0=Completion, 1=Success, 2=Failure, 3=Creation. |
|
UsrMsk |
No |
User bit mask specifies the user bit mask of the point to update. |
|
UsrVal |
No |
User bit value to match specifies the user bit value to match when updating the point record. |
|
Value |
No |
Value indicates the point value to update. |
CYWAITPT
Wait for CygNet Point signals the UIS to wait to perform a command until the value of the specified CygNet point changes to a specified value.
CYWAITPT must be the first command component added to a UIS command. You cannot add other instances of CYWAITPT to a UIS command.
CYWAITPT has the following command parameters:
| Parameter | Required | Description |
|---|---|---|
|
Dur |
Yes |
Duration is the amount of time (in HH:MM:SS or HH:MM or HH) for the UIS command to wait for the point value to change before timing out. |
|
FOnErr |
No |
Fail on point error indicates to abort the UIS command if any error conditions are encountered. The point errors that might come up include: if the point specified in the Fac, Serv, Site, or UDC parameters does not exist, or if the point exists in a different UIS and any messaging errors or communication failure to that service comes up. |
|
Fac |
Yes |
Facility for pt identifies the facility of the point on which to wait for the point value to change before performing the UIS command. |
|
Int |
Yes |
Interval indicates the frequency (in HH:MM:SS or HH:MM or HH) with which the UIS will check the point’s value to see if it has changed. |
|
Serv |
No |
Service for pt identifies the SERVICE of the point on which to wait for the point value to change before performing the UIS command. |
|
Site |
No |
Site for pt identifies the SITE of the point on which to wait for the point value to change before performing the UIS command. |
|
UDC |
Yes |
UDC for pt identifies the UDC of the point on which to wait for the point value to change before performing the UIS command. |
|
UsrMsk |
No |
User bit mask specifies the user bit mask on which to wait for the status bit change before issuing the UIS command. Note: The user status bit parameters (UsrMsk and UsrVal) only apply to the extended status field of the point record, so they will not match anything in the base status. |
|
UsrVal |
No |
User bit value to match specifies the user bit value to match before issuing the UIS command. |
|
Value |
No |
Value to match specifies the value on which to wait for the point to change to before issuing the UIS command. Note: You can set parameters for both the point user status AND point value. So you can match either one by itself, or you can specify that both must match your parameter values. |
DG_F_DEV
Get data group from device retrieves a data group from a field device. The Parent XML Element is uccRecvParms. The following parameters are available for each specified data group type.
| Data Group Type | Parameter | Required | Description | Value Options |
|---|---|---|---|---|
|
Date |
Yes |
History Date enables you to specify the calendar day by which to collect historical data. |
Strings in formats described in Selecting Date and Time. |
|
|
EDate |
Yes |
End Contract Date defines the ending contract time and date for a date-range request. |
Strings in formats described in Selecting Date and Time. |
|
|
SDate |
Yes |
Start Contract Date defines the starting contract time and date for a date-range request. |
Strings in formats described in Selecting Date and Time. |
|
|
EDate |
Yes |
End Contract Date defines the ending contract time and date for a date-range request. |
Strings in formats described in Selecting Date and Time. |
|
|
GetLatest |
No |
Get Latest? defines whether or not to retrieve history from the latest successfully read history record (the cache). Note: If you specify GetLatest="true", a start date or end date is not required. If GetLatest="false", a start date is required. For more information, see History Retrieval Optimization. |
Boolean |
|
|
ReqClosed |
No |
Request Closed Days Only requests any completed contract day for which all applicable CTD history records have been generated by the field device and no further CTD history records or events are added. |
Boolean |
|
|
ReqExt |
No |
Request Sum of Extensions requests the CTD history sum of extensions. Sum of extensions is also known as integral value, which is the terminology typically used by CygNet. |
Boolean |
|
|
SDate |
Yes |
Start Contract Date defines the starting contract time and date for a date-range request. |
Strings in formats described in Selecting Date and Time. |
|
|
EDate |
No |
End Device Date defines the ending device date and time of a date-range request. |
Strings in formats described in Selecting Date and Time. |
|
|
SDate |
Yes |
Start Device Date defines the starting device date and time of a date-range request. |
Strings in formats described in Selecting Date and Time. |
|
|
EDate |
No |
End Device Date defines the ending device date and time of a date-range request. |
Strings in formats described in Selecting Date and Time. |
|
|
SDate |
Yes |
Start Device Date defines the starting device date and time of a date-range request. |
Strings in formats described in Selecting Date and Time. |
|
|
EDate |
Yes |
End Device Date defines the ending device date and time of a date-range request. |
Strings in formats described in Selecting Date and Time. |
|
|
SDate |
Yes |
Start Device Date defines the starting device date and time of a date-range request. |
Strings in formats described in Selecting Date and Time. |
|
|
EDate |
Yes |
End Device Date defines the ending device date and time of a date-range request. |
Strings in formats described in Selecting Date and Time. |
|
|
SDate |
Yes |
Start Device Date defines the starting device date and time of a date-range request. |
Strings in formats described in Selecting Date and Time. |
|
|
Date |
Yes |
Production History Date enables you to specify the calendar day by which to collect historical data. |
Strings in formats described in Selecting Date and Time. |
|
|
Date |
Yes |
Days Back enables you to specify the number of passed days by which to collect historical data. |
Strings in formats described in Selecting Date and Time. |
|
|
ETime |
No |
Ending Trend Hour defines the ending time for a time-range request. |
Strings in formats described in Selecting Date and Time. |
|
|
Time |
No |
Starting Trend Hour defines the starting time for a time-range request. |
Strings in formats described in Selecting Date and Time. |
DG_T_DEV
Send data group to device sends a data group to a field device. The parent XML Element is uccSendParms. The following parameters are available for each specified data group type.
| Data Group Type | Parameter | Required | Description | Value Options |
|---|---|---|---|---|
|
Time |
Yes |
Contract Hour defines the contract hour to be sent to a field device. |
Integer value 0 - 23 |
|
|
State |
Yes |
Action (Latch, Unlatch, Pulse) enables you to change the Action state setting. |
Strings |
|
|
Time |
No |
Pulse Duration enables you to set the pulse duration when Action is set to Pulse. |
Integers |
|
|
FCSetpoint |
Yes |
Setpoint enables you to set the flow control setpoint value. |
Integers |
|
|
Val1 |
Yes |
Old Password enables you to specify the old password. |
Strings |
|
|
Val2 |
Yes |
New Password enables you to specify the new password. |
Strings |
|
|
Val1 |
Yes |
Set Point Value enables you to set the analog output setpoint value. |
Integers |
GETTIME
Get RTU Time retrieves time from the field device. GETTIME has no command parameters.
SETTIME
Set RTU Time sets time for the field device. SETTIME has no command parameters.
STATUS
Get Current Status retrieves current status from the field device. STATUS has no command parameters.